OUR PRODUCTS:
|
| Type:
DHC-100 |
| |
|
DHC-100
adopts the integrated circuit type humidity sensor, with all
the advantages of high sensitivity, fast response and excellent
coherence, mainly used to measure, display and control the humidity.
It specifies all the functions such as: switch the modes between
humidification and dehumidification; control humidity by setting
value and the difference value; output delay protection; calibrate
the humidity value; alarm when sensor or when humidity
exceeds limit; proportional running time and stop time are adjustable
when sensor error, keypad lock function. |
| |
SPECIFICATION
AND TECHNICAL PARAMETER:
- Whole
product size: 34.5x75x85.5 (mm)
- Installing-hole
size: 28.8x70 (mm)
- Operation
environment temperature: 0°C~+55°C
- Relative
humidity: 20%~85% (No condensate)
- Main
technical parameter:
- Power supply: 220VAC±10%/-15%
- Power consumption: <3W
- Humidity measuring range: 1%~99%RH
- Humidity controlling range: 10%~95%RH
- Resolution: 1%RH
- Accuracy: ±5%RH(10%RH~95%RH, 25°C)
- Sensor operating temperature range:
-30°C~+80°C
- Temperature coefficient: ±0.2%RH/°C
- Extended stability: 0.5%RH/yr
- Relay contact capacity: 10A/220VAC
|
| |
| MENU
INSTRUCTION |
Code |
Function |
Set
range |
Unit |
Default |
F1 |
Umidity
set value |
10~99 |
%RH |
50 |
F2 |
Umidity
difference value |
1~50 |
%RH |
5 |
F3 |
Output
delay protection time |
0~99 |
min |
0 |
F4 |
Alarm
deviation value, set "0" to canceled |
0~50 |
%RH |
0 |
F5 |
Proportional
running time when sensor error |
0~99 |
min |
10 |
F6 |
Proportional
stop time when sensor error |
0~99 |
min |
50 |
F7 |
Humidity
calibration value for end user |
-20~20 |
%RH |
0 |
F8 |
Controller
work mode, 0: humidification; 1:dehumidification |
0~1 |
---- |
0 |
b1 |
The
first two figures of "Zero offset" |
5000~9999 |
0.1mV |
---- |
b2 |
The
last two figures of "Zero offset" |
k1 |
The
first two figures of "Slope" |
2000~39999 |
0.01mV/%RH |
---- |
k2 |
The
las two figures of "Slope" |
WIRING
DIAGRAM  |
| |
| 2
mt cable external humidity probe included |
|
| 27x35x12
mm Humidity control: 1%~99% |
|
|
 |