Code |
Meaning |
Range |
Unit |
Defaul |
F01 |
Set temp. upper limit |
-39~+110 |
°C |
-15 |
F02 |
Set temp. lower limit |
-40~109°C |
°C |
-20 |
F03 |
Set alarming values when exceeding the
temp. limits |
0~20 |
°C |
10 |
F04 |
Fast refrigeration time |
0~20 |
Hour |
4 |
F05
| Compressor start delayed |
0~20 |
Minute |
3 |
F06 |
Defrosting interval (cycle) |
0~99 |
Hour |
6 |
F07 |
Defrosting time |
0~99 |
Minute |
30 |
F08 |
Temperature when the defrosting process
ends |
-40~+50 |
°C |
10 |
F09 |
Temperature when the fan stops working |
-40~+50 |
°C |
2 |
F10 |
Temp. calibration |
-5~+5 |
°C |
0 |
F11 |
Time for defrosting and water dropping |
0-99 |
Minute |
3 |
F12 |
Fan's delayed operation after defrosting
and being electrified |
0-99 |
Minute |
10 |
F13 |
Alarm delayed when exceeding temp. limit |
0-99 |
Minute |
15 |
F14 |
Delay when sensor error |
0-20 |
Minute |
1 |
F15 |
Compressor start working when sensor error |
0-99 |
Minute |
15 |
F16 |
Compressor stops working when sensor error |
0-99 |
Minute |
30 |
F17 |
Defrosting mode |
0: electri-heat defrost |
|
0 |
1: Thermal defrost |
F18 |
Fan's operation mode |
0: work or stop together
with compressor (Stop when to defrost) |
|
0 |
1: continuous working (stops
when to defrost) |
F19 |
Refrigeration / heating mode |
0: refrigeration mode |
|
0 |
1: heating mode |
|
Alarms when temperature is higher than
upper limit |
HHH |
°C |
>+110 |
|
Alarm when temperature is lower than bottom
limit |
LLL |
°C |
<-40 |