OUR PRODUCTS:
|
| |
|

|
ETC-300 |
| |
|
| |
| SPECIFICATIONS |
- Small size, double sensor, with complete functions, suitable
for all kinds of refrigerated storage which needs complex measuring
and controlling of temperature
- Defrosting type options: electric-heat or thermal
- Switch between modes of refrigerating and heating
- Fan control: start/stop simultaneously with the compressor or
continuous running
- Defrost controlled by time and temperature
- Power supply 110/220VAC ± 10%, 50~60HZ
- Resolution 0.1°C
- Realy contact capacity 10A/240VAC
- Ambient temperature 60°C
- Relative humidity 10%~95% (no condensate)
- Hole size 70.5x28.5 mm
- Measuring range -50°C ~ 50°C
- Accuracy ± 0.5°C (-10°C~10°C)
- Other range: <± 1°C
- Product size 75x34.5x50 mm
- Sensor NTC
|
| |
| Code |
Meaning |
Range |
Unit |
Defaul |
| F01 |
Set temp. upper limit |
-49~+120 |
°C |
-15 |
| F02 |
Set temp. lower limit |
-50~119°C |
°C |
-18 |
| F03 |
Exceedeng Temp. alarm |
0~20 |
°C |
10 |
| F04 |
Compressor delay time |
0~9 |
Min. |
3 |
F05
| Defrosting cycle |
0~99 |
hours |
6 |
F06 |
Defrosting time |
0~99 |
Min. |
30 |
F07 |
Defrosting end time |
-50~+50 |
°C |
10 |
F08 |
Storage Temp. calibration |
-5~+5 |
°C |
2 |
F09 |
Fan ending temp. |
|
|
|
F10 |
Defrosting mode |
0: Electric heating |
|
0 |
1: Thermal |
F11 |
Fan mode |
0: start/stop with compressor
simultaneously |
|
0 |
1: continualy run |
|
| |
| |
| |
|
|
|
 |